Delta-electronics Extension Digital I/O Module DOP-EXIO14RAE Manual do Utilizador Página 76

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 157
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 75
Appendix C Use of Basic Instructions|DOP-EXIO Series
Revision March, 2008, Doc. Name: 2007PDD23000014 C-11
Program Example:
Ladder diagram: Instruction code: Operation:
LD X0 Loading in A contact of X0
ANDF X1 X1 falling-edge detection in series
connection
X1X0
Y1
OUT Y1 Drive Y1 coil
Mnemonic Functions
ORP
Rising-edge Parallel Connection
X0~X17 Y0~Y17 M0~M1279 S0~S127 T0~T127 C0~C254 D0~D599
Operand
9 9 9 9 9 9
-
Explanations:
The ORP instructions are used in the parallel connection of the contact’s rising-edge detection.
Program Example:
Ladder diagram: Instruction code: Operation:
LD X0 Loading in A contact of X0
ORP X1 X1 rising-edge detection in parallel
connection
X0
X1
Y1
OUT Y1 Driving Y1 coil
Mnemonic Functions
ORF
Falling-edge Parallel Connection
X0~X17 Y0~Y17 M0~M1279 S0~S127 T0~T127 C0~C254 D0~D599
Operand
9 9 9 9 9 9
-
Explanations:
The ORF instructions are used in the parallel connection of the contact’s falling-edge detection.
Program Example:
Ladder diagram: Instruction code: Operation:
LD X0 Loading in A contact of X0
ORF X1 X1 falling-edge detection in parallel
connection
X0
X1
Y1
OUT Y1 Driving Y1 coil
Vista de página 75
1 2 ... 71 72 73 74 75 76 77 78 79 80 81 ... 156 157

Comentários a estes Manuais

Sem comentários