English- 6
Power Terminals
Motor
Connection
Ground Braking Resistor
AC Input Line
Ter minal
AC Input Line
Terminal
Motor
Conne ction
Braking ResistorGround
Figure 1: VFD002S11A/11B, VFD004S11A/11B Figure 2: VFD007S11A/B
DC Reactor
Braking
Resistor
Ground
AC Input Line
Ter minal
Motor
Conne ction
AC Input Line
Terminal
Ground DC Reactor
Braking
Resistor
Motor
Connection
Figure 3: VFD002S21A/E, VFD004S21A/E,
VFD007S21A/E
Figure 4: VFD002S21B/23A,
VFD004S21B/23A/43A/43B/43E,
VFD007S21B/23A/43A/43B/43E, VFD015S23D
A
C Input Line
Te r m in al
Mot o r
Connection
DC Reactor
Brak ing
Resistor
Ground
Braking
Resistor
DC ReactorGround
AC Input Line
Te r mi n a l
Motor
Connection
Figure 5: VFD015S21U/43D/43E/43U,
VFD022S21U/23D/43D/43E/43U
Figure 6: VFD015S21D/E, VFD022S21D/E
Figure 1/figure3/figure 4:
Wire Gauge: 14-20 AWG (2.1-0.5mm
2
)
Wire Type: copper wire only, 75°C
Torque: 12 kgf-cm (10 in-lbf)
Figure 2/figure5/figure 6:
Wire Gauge: 10-18 AWG (5.3-0.8mm
2
)
Wire Type: stranded copper wire only, 75°C
Torque: 20 kgf-cm (17.4 in-lbf)