9 Application Instructions API 150-199
DVP-PLC Application Manual
9-29
D1336
For EH/EH2/SV, low word of the current number of output pulses from CH0.
D1337
For EH/EH2/SV, high word of the current number of output pulses from CH0.
D1338
For EH/EH2/SV, low word of the current number of output pulses from CH1.
D1339
For EH/EH2/SV, high word of the current number of output pulses from CH1.
D1340
For EH/EH2/SV, settings of the first start frequency and the last end frequency of CH0.
D1343
For EH/EH2/SV, settings of acceleration/deceleration time for CH0 pulse output.
D1352
For EH/EH2/SV, settings of the first start frequency and the last end frequency of CH1.
D1353
For EH/EH2/SV, settings of acceleration/deceleration time for CH1 pulse output.
D1375
For EH2/SV, low word of the current number of output pulses from CH2.
D1376
For EH2/SV, high word of the current number of output pulses from CH2.
D1377
For EH2/SV, low word of the current number of output pulses from CH3.
D1378
For EH2/SV, high word of the current number of output pulses from CH3.
D1379
For EH2/SV, settings of the first start frequency and the last end frequency of CH2.
D1380
For EH2/SV, settings of the first start frequency and the last end frequency of CH3.
D1348 For EH2/SV, deceleration time for CH0 pulse output when M1534 = On.
D1349 For EH2/SV, deceleration time for CH1 pulse output when M1535 = On.
D1350 For EH2/SV, deceleration time for CH2 pulse output when M1536 = On.
D1351 For EH2/SV, deceleration time for CH3 pulse output when M1537 = On.
D1381 For EH2/SV, settings of acceleration/deceleration time for CH2 pulse output.
D1382 For EH2/SV, settings of acceleration/deceleration time for CH3 pulse output.
D1383 For EH2/SV, the time difference between the direction signal and pulse output sent by CH2.
D1384 For EH2/SV, the time difference between the direction signal and pulse output sent by CH3.