VFD-M Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
3-4
3.3
Control Terminal Wiring (Factory Settings)
M0 M1 M2
M3
M4
M5
GND AFM
AVI
+10V
MCM
M01
RA RB RC
Relay contactor
Output
Factory Setting
Bias
Potentiometer
Full scale voltmeter
0 to 10 VDC
Factory setting:
fault indication
Photo coupler
output
Forward/Stop
Reverse/Stop
Reset
Multi-step speed 1
Multi-step speed 2
Multi-step speed 3
ACI
GND
4~20mA
Wire Type: 75 C, Copper Only
Torque: 4kgf-cm (3.5 in-lbf)
Wire Gauge: 24-12 AWG
Wire Type: Copper Only
Torque: 2.5kgf-cm (2.2 in-lbf)
Wire Gauge: 22-16 AWG
Terminal
symbols
Terminal name Remarks
RA – RC
Multi-Function Indication Output
Contact
RB – RC
Multi-Function Indication Output
Contact
Refer to Pr.46 Relay output contact
RA-RC (N.O. Contact)
RB-RC (N.C. Contact)
MO1 -MCM Multi-function PHC output Refer to Pr.45
RJ – 11 Serial communication port RS-485 serial communication interface
+10V - GND Power Supply (+10 V)
AVI - GND
Analog voltage freq. command
0 to +10 V (Max. Output Frequency) Input
ACI - GND
Analog current freq. command
4 to 20mA (Max. Output Frequency) Output
AFM - GND
Analog frequency/current meter
0 to +10 V (Max. output Frequency) Output
M0 - GND
Multi-function auxiliary input
M1 - GND
Multi-function input 1
To
To
M5 - GND
Multi-function input 5
Refer to Pr.38 to Pr.42
Note:
Use twisted-shielded, twisted-pair or shielded-lead wires for the control signal wiring. It
is recommended to run all signal wiring in a separate steel conduit. The shield wire
should only be connected at the drive. Do not connect shield wire on both ends.