CR#
HW LW
Attribute Content Explanation
#19 #18 R
Error status of slaves in
data exchange
0: No error occurs.
1: An error occurs in data exchange.
b0~b15 in CR#19: States of slave 1~slave 16.
b0~b8 in CR#18: States of slave 17~slave 24.
#24~#20 - Reserved
#26 #25 R/W Destination IP address Destination IP address for data exchange
#27 -
Function code for a data
exchange mode
0 (Default value): The function of function code 17 is enabled.
1: The function of function code 17 is disabled.
#28 R/W Destination Slave ID Destination Slave ID for data exchange
#48~#29 R/W Data transmission buffer Buffer for transmitted data in data exchange
#68~#49 R Data receiving buffer Buffer for received data in data exchange
#80~#69 - Reserved
#81 R/W
Read address for data
exchange
Slave transmission buffer address for data exchange
#82 R/W
Read length for data
exchange
Number of registers for read data
#83 R/W
Received address for
data exchange
Buffer address for the receiving Master in data exchange
#84 R/W
Written-in address for
data exchange
Buffer address for the receiving Slave in data exchange
#85 R/W
Written-in length for data
exchange
Number of registers for data transmission
#86 R/W
Transmission address
for data exchange
Master transmission buffer address for data exchange
#87 R/W
Mode of setting an IP
address
0: Static IP address
1: DHCP
#89 #88 R/W IP address Setting an IP address
#91 #90 R/W Netmask Setting a netmask
#93 #92 R/W Gateway IP address Setting a gateway IP address
#94 R/W
Enabling the setting of
an IP address
Executing the setting of an IP address
#95 R
Status of setting an IP
address
Showing the status of setting an IP address
0: The setting of an IP address is successful.
1: The setting of an IP address fails.
#101~#96 - Reserved
#102 R/W MC Protocol UDP port
Setting the UDP port of an MC protocol data exchange slave
(Default value: 1025)
#110~#103 - Reserved
#111 R/W 8-bit processing mode Setting the MODBUS TCP master control as 8-bit mode
#112 R/W
MODBUS TCP
Keepalive time
MODBUS TCP Keepalive time (Unit: Second)
#113 - Reserved
#114 R/W MODBUS TCP timeout Setting the MODBUS TCP timeout (Unit: Millisecond)
#115 R/W MODBUS TCP trigger Setting whether to send out data in MODBUS TCP mode
#116 R/W MODBUS TCP status Displaying current status of MODBUS TCP mode
#118 #117 R/W
MODBUS TCP
destination IP address
Setting a destination IP address for MODBUS TCP transaction
#119 R/W
MODBUS TCP data
length
Setting the data length for MODBUS TCP transaction
#219~#120 R/W
MODBUS TCP data
buffer
Data buffer of MODBUS TCP for storing sending/receiving data
#248~#220 - Reserved
#251 R Error code
Displaying the errors. See table of error codes in the following
section for more information.
#255~#252 - Reserved
Symbols “R” refers to “able to read data by FROM instrcution”; “W” refers to “able to write data by TO instrcution”.