English-15
Parameter Functions Settings
Factory
Setting
Customer
a01-14 Deceleration Time 3 0.1~3600.0 Sec 10.0/
60.0
a01-15 Acceleration Time 4 0.1~3600.0 Sec 10.0/
60.0
a01-16 Deceleration Time 4 0.1~3600.0 Sec 10.0/
60.0
a01-17 JOG Acceleration Time 0.1~3600.0 Sec 10.0/
60.0
a01-18 JOG Deceleration Time 0.1~3600.0 Sec 10.0/
60.0
a01-19 JOG frequency 0.0 Hz~120.00 Hz 6.00
01-20 S Curve Delay Time in
Accel
0.00~2.50sec 0.00
01-21 S Curve Delay Time in
Decel
0.00~2.50sec 0.00
a01-22 Modulation Index 0.90~1.20 1.00
01-23 Accel/Decel Time Unit 00: Unit is 1 Sec
01: Unit is 0.1 Sec
02: Unit is 0.01 Sec
01
Group 2 Digital Output/Input Parameter
Parameter Functions Settings
Factory
Setting
Customer
a02-00 Source of Frequency
Command
00: via keypad
01: via analog input AVI
02: via analog input ACI1
03: via analog input ACI2
04: via RS485 serial communication
05: via External Reference
00
a02-01 Source of Operation
Command
00: Controlled by the digital keypad
01: Controlled by the external terminals,
keypad STOP enabled.
02: Controlled by external terminals,
keypad STOP disabled.
03: Controlled by the RS-485
communication interface, keypad
STOP enabled.
04: Controlled by the RS-485
communication interface, keypad
STOP disabled.
00
02-02 Stop Method 00:Stop = ramp to stop, E.F. (External
Fault) = coast to stop
01:Stop = coast to stop, E.F. = coast to
stop
02:Stop = ramp to stop, E.F. = ramp to
stop
03:Stop = coast to stop, E.F. = ramp to
stop
00
a02-03 PWM Carrier Frequency
Selections
1~10HP: 4000~10000Hz
15~30HP: 3000~9000Hz
40HP: 2000~6000Hz
9000Hz
6000Hz
4000Hz