English-20
Parameter Functions Settings
Factory
Setting
Customer
a05-14 15
th
Step Speed
Frequency
0.00~120.00 Hz 0.00
05-15 PLC Mode
00: Disable PLC Operation
01: Execute one program cycle
02: Continuously execute program cycles
03: Execute one program cycle step by
step
04: Continuously execute program cycles
step by step
00
05-16 PLC Forward/ Reverse
Motion
00 to 32767 (00: FWD 01: REV) 00
05-17 Time Duration Step 1 0.0 to 65500 sec 0.0
05-18 Time Duration Step 2 0.0 to 65500 sec 0.0
05-19 Time Duration Step 3 0.0 to 65500 sec 0.0
05-20 Time Duration Step 4 0.0 to 65500 sec 0.0
05-21 Time Duration Step 5 0.0 to 65500 sec 0.0
05-22 Time Duration Step 6 0.0 to 65500 sec 0.0
05-23 Time Duration Step 7 0.0 to 65500 sec 0.0
05-24 Time Duration Step 8 0.0 to 65500 Sec 0.0
05-25 Time Duration Step 9 0.0 to 65500 Sec 0.0
05-26 Time Duration Step 10 0.0 to 65500 Sec 0.0
05-27 Time Duration Step 11 0.0 to 65500 Sec 0.0
05-28 Time Duration Step 12 0.0 to 65500 Sec 0.0
05-29 Time Duration Step 13 0.0 to 65500 Sec 0.0
05-30 Time Duration Step 14 0.0 to 65500 Sec 0.0
05-31 Time Duration Step 15 0.0 to 65500 Sec 0.0
05-32 Time Unit Settings
00: 1 Sec
01: 0.1 Sec
00
Group 6 Protection Function Parameters (Twice the value for 460V class)
Parameter Functions Settings
Factory
Setting
Customer
06-00 Over-voltage Stall
Prevention
230V: 330.0~410.0VDC
460V: 660.0~820.0VDC
00: Disable
390.0
780.0
06-01 Over-current Stall
Prevention during
Acceleration
20~150%
00: Disable
120
06-02 Over-current Stall
Prevention during
operation
20~150%
00: Disable
120