Chapter 7 Servo Parameters|ASDA-B Series
7-82 Revision January, 2009
DO Name DO Function Description Control Mode
OLW
Result:
When the drive output is at 200% rated output and the drive is
continuously overloaded for 4.8 seconds, and the overload warning
signal will be ON (DO code is 10, i.e. DO signal OLW will be activated).
If the drive is continuously overloaded for 8 seconds, the overload alarm
will be detected and shown on the LED display (ALE06). Then, Servo
Fault signal will be ON (DO signal ALRM will be activated)
P, S, T
Setting value of P2-18 ~ P2-20: 10
DO Name DO Function Description Control Mode
WARN
Servo warning activated. WARN is activated when the drive has
detected Reverse limit error, Forward limit error, Emergency stop, Serial
communication error, and Undervoltage these fault conditions.
P, S, T
NOTE
1) When P2-18 to P2-20 is set to 0, it indicates output function is disabled.