8
VFD-V Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-3
Control Mode
Parameters Functions Settings
Factory
Setting
VF VG SV SG T TG
a
00-04
Definitions of the
Multi-Function
Display
85: Input position of pulse
(Channel 2)
86: OL3 timer
0
{ { { { { {
a
00-05
User-Defined
Coefficient
Setting
4 digit: 0-3: the number of the
decimal places
3-0 digit: 40~9999
0
{ { { { { {
00-06 Software Version Read-only
a
00-07 Password Input 0~9999 0
{ { { { { {
a
00-08 Password Setting 0~9999 0
{ { { { { {
a
00- 09
Frequency and
the Operation
Method of PU05
Bit0=0: Frequency via the up/down
keys
Bit0=1: Frequency command
enabled after pressing the
data/prog key
Bit1=0: PU05&RS485 frequency
memorized
Bit1=1: PU05&RS485 frequency
not memorized
Bit2=0: Up/down pin frequency
memorized
Bit2=1: Up/down pin frequency not
memorized
Bit3=0: FWD/REV direction
memorized
Bit3=1: FWD/REV direction not
memorized
Bit4=0: Parameter memorized
Bit4=1: Parameter not memorized
00000
{ { { { { {
0: V/F Control
{ ° ° ° ° °
1: V/F Control + PG
° { ° ° ° °
2: Vector Control (open loop)
° ° { ° ° °
3: Vector Control + PG (closed
loop)
° ° ° { ° °
4: Torque Control
° ° ° ° { °
00-10 Control Methods
5: Torque Control + PG
0
° ° ° ° ° {
00-11
Forward Reverse
transition in V/F
mode
0: Follow Pr. 01-00 to 01-08
Settings
1: Follow Pr. 01-00 to 01-08
Settings
2: V/F1.5 power curve (Do not skip
the start-up frequency)
3: V/F1.5 power curve (skip)
4: 2 power curve (do not skip)
5: 2 power curve (skip)
0
{ { ° ° ° °
http://www.automatedpt.com
http://www.automatedpt.com
Comentários a estes Manuais