Delta Electronics AC Motor Drive VFD-VE Series Especificações Página 45

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 182
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 44
5
VFD-V Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-17
Frequency
1st/4th Acceleration/Deceleration Switching
01-23
4th Acceleration Time
4th Deceleration
Time
1st Acceleration
Time
1st Deceleration
Time
1st/4th
Acceleration
/Deceleration
Freq.
01-24 S-Curve for Acceleration Departure Time
a
Factory setting 0.00
01-25 S-Curve for Acceleration Arrival Time
a
Factory setting 0.00
01-26 S-Curve for Deceleration Departure Time
a
Factory setting 0.00
01-27 S-Curve for Deceleration Arrival Time
a
Factory setting 0.00
Settings 0.00~25.00 Sec/0.0~250.0 Sec
This parameter determines the S curve strength. A large S curve time will give the
smoothest transition between speed changes. Please note the S curve settings
increase the actual acceleration/deceleration times as follows:
Actual acceleration time = [½(Pr.01-24) + ½(Pr.01-25) + Pr.01-12]
The S curve is disabled when Pr. 00-13 (Auto Acceleration/Deceleration Speed
Selection) is set to Auto or Pr 01-12 to 01-19 (acceleration/deceleration times) is set to