VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-6
1 - 03 Középponti frekvencia (Fmid) Factory Setting: d 1.0
Settings d 1.0 to d 400Hz Unit: 0.1Hz
! This parameter sets the Mid-Point Frequency of V/F curve. With this setting, the V/F
ratio between Minimum Frequency and Mid-Point frequency can be determined. This
parameter must be greater than or equal to Minimum Output Frequency (Pr.1-05) and
equal to or less than Maximum Voltage Frequency (Pr.1-01).
1 - 04 Középponti feszültség (Vmid) Factory Setting: d12.0*
Settings d 2.0 to d 255V* Unit: 0.1V*
*Twice value for 460V class
! The parameter sets the Mid-Point Voltage of any V/F curve. With this setting, the V/F ratio
between Minimum Frequency and Mid-Point Frequency can be determined. This
parameter must be equal to or greater than Minimum Output Voltage (Pr.1-06) and equal
to or less than Maximum Output Voltage (Pr.1-02).
1 - 05 Minimum kimeneti frekvencia (Fmin) Factory Setting: d 1.0
Settings d 1.0 to d 60.0Hz Unit: 0.1Hz
! This parameter sets the Minimum Output Frequency of the AC drive. This parameter
must be equal to or less than Mid-Point Frequency (Pr.1-03).