Delta Electronics Network Device VFD-S Especificações Página 32

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 130
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 31
5
VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-15
2 - 04 Hátraforgási irány engedélyezése / Tiltása Factory Setting: d 0
Settings d 0 Enable REV operation
d 1 Disable REV operation
! The parameter determines whether the AC drive can operate in the reverse direction.
2 - 05 Loss of ACI Signal Factory Setting: d 0
Settings d 0 Upon the loss of ACI, the drive will default to an output
frequency of 0 Hz.
d 1 Upon the loss of ACI, the drive will stop and display error
message “EF”.
d 2 Upon the loss of ACI, the drive will continue to run at the last
known ACI input.
! This parameter is only effective when the Source of Frequency is commanded by a 4 to
20 mA signal. The ACI input is considered lost when the ACI signal falls below 2 mA.
2 - 06 Analog Auxiliary Frequency Operation Factory Setting: d 0
Settings d 0 Disable
d 1 Enable + AVI (0~10V)
d 2 Enable + ACI (4~20mA)
! This parameter is used to determinate that the analog signal to overlap is 0~10V (AVI) or
4~20mA (ACI).
! To make sure the short PIN of J1 on the panel is correct position before setting this
parameter.
Vista de página 31
1 2 ... 27 28 29 30 31 32 33 34 35 36 37 ... 129 130

Comentários a estes Manuais

Sem comentários