5.6 Group 5: Multi-step Speed and PLC (Process Logic Control) Parameters
5 - 00 1st Step Speed Frequency Factory Setting: d 0.0
5 - 01 2nd Step Speed Frequency Factory Setting: d 0.0
5 - 02 3rd Step Speed Frequency Factory Setting: d 0.0
5 - 03 4th Step Speed Frequency Factory Setting: d 0.0
5 - 04 5th Step Speed Frequency Factory Setting: d 0.0
5 - 05 6th Step Speed Frequency Factory Setting: d 0.0
5 - 06 7th Step Speed Frequency Factory Setting: d 0.0
Settings d 0.0 to d 400 Hz Unit: 0.1Hz
This parameter can be set during operation.
! The Multi-Function Input Terminals (refer to Pr.4-04 to 4-08) are used to select one of the
AC drive Multi-Step speeds. The speeds (frequencies) are determined by Pr.5-00 to
5-06 shown above.
5 – 07 PLC Mode Factory Setting: d 0
Settings d 0 Disable PLC operation
d 1 Execute one program cycle
d 2 Continuously execute program cycles
d 3 Execute one program cycle step by step
d 4 Continuously execute program cycles step by step
d 5 Disable PLC operation, but can set direction of 1
st
speed to 7
th
speed
! This parameter selects the mode of PLC operation for the AC drive. The PLC program
can be used in lieu of any External Controls, Relays or Switches. The AC drive will
change speeds and directions according to the user’s desired programming.
! When this parameter is set to d5 and it is running by external multi-speed, the high priority
of the operation direction is Pr. 5-08.