VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-7
Parameters Explanation Settings
Factory
Setting
4-09 Line Start Lockout
d0: Disable
d1: Enable
d0
4-10
Up/down frequency
command mode
d0: Up/down frequency by
acceleration/deceleration time
d1: Up frequency according to constant
speed, down frequency according to
deceleration time
d2: Up frequency according to acceleration
time, down frequenc according to constant
speed
d3: Up/down frequency by constant speed
d3
4-11
Acceleration
/Deceleration speed of
constant up/down
frequency
d0 to d1000 Hz/sec d1