5
VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-7
1 - 06 Minimum Output Voltage (Vmin) Factory Setting: d12.0*
Settings d 2.0 to d 255V* Unit: 0.1V*
*Twice value for 460V class
This parameter sets Minimum Output Voltage of the AC drive. This parameter must be
equal to or less than Mid-Point Voltage (Pr.1-04).
Voltage
Pr.1-02
Pr.1-04
Pr.1-06
0
Pr.1-03
Pr.1-05
Pr.1-00
Pr.1-01
Freq.
Standard V/F Curve
1 - 07 Upper Bound of Output Frequency Factory Setting: d 100
Settings d 1 to d110% Unit: 1%
This parameter must be equal to or greater than the Lower Bound of Output Frequency
(Pr.1-08). The Maximum Output Frequency (Pr.1-00) is regarded as 100%.
1 - 08 Lower Bound of Output Frequency Factory Setting: d 0
Settings d 0 to d100% Unit: 1%
The Upper/Lower Bound is to prevent operation error and machine damage.
If the Upper Bound of Output Frequency is 50Hz and the Maximum Output Frequency is
60Hz, the Maximum Output Frequency will be limited to 50Hz.
If the Lower Bound of Output Frequency is 10Hz, and the Minimum Output Frequency
(Pr.1-05) is set at 1.0Hz, then any Command Frequency between 1-10Hz will generate
a 10Hz output from the drive.
This parameter must be equal to or less than the Upper Bound of Output Frequency
(Pr.1-07).